Description
Part Number: 3051CD2F02A1AH2B1IAT1DFQ4
- Power advisory can proactively detect degraded electrical loop integrity issues(option code DA0)
- LOI with straightforward menus and built-in configuration buttons (option code M4)
- Safety Certification (option code QT)
Ordering Information
| Model | 3051C(1) | Coplanar Pressure Transmitter |
| Measurement type | D | Differential |
| Pressure range | 2 | –250 to 250 inH2O (-621,60 to 621,60 mbar) |
| Transmitter output | F | FOUNDATION™ fieldbus Protocol |
| Materials of construction | 0 | Alternate Process Connection |
| Isolating diaphragm | 2(2) | 316L SST |
| O-ring | A | Glass-filled PTFE |
| Sensor fill fluid | 1 | Silicone |
| A | Housing material: Aluminum Conduit entry size: ½–14 NPT |
|
| Alternate flange(3) | H2 | Traditional Flange, 316 SST, SST drain/vent |
| Mounting bracket(4) | B1 | Traditional flange bracket, CS, 2-in. pipe |
| Product certifications | IA | ATEX FISCO Intrinsic Safety; for FOUNDATION fieldbus or PROFIBUS PA protocol only |
| Transient protection | T1(5)(6) | Transient Protection Terminal Block |
| Flange adapters | DF(7) | 1 /2 -14 NPT flange adapter(s) |
| Calibration certificate | Q4 | Calibration Certificate |
- Select Configuration Buttons (option code D4 or DZ) or Local Operator Interface (option code M4) if local configuration buttons are required.
- Materials of Construction comply with recommendations per NACE MR0175/ISO 15156 for sour oil field production environments. Environmental limits apply to
certain materials. Consult latest standard for details. Selected materials also conform to NACE MR0103 for sour refining environments. - Requires 0 code in Materials of Construction for Alternate Process Connection.
- Panel mounting bolts are not supplied.
- Not available with Wireless Output (code X).
- The T1 option is not needed with FISCO Product Certifications; transient protection is included in the FISCO product certification codes IA, IB, and IE.
- Not valid with Alternate Process Connection options S3, S4, S5, and S6.
- Estimated Lead Time: 8 Weeks
- Shipping Weight: 6 Kg

Rosemount
Gauge Pressure
Differential Pressure
Absolute Pressure
Rosemount Level Transmitter
Yokogawa
ABB
E+H
HoneyWell
Micro Motion Coriolis
Rosemount
Yokogawa
E+H





Valves&Actuators