Description
- Dual-compartment field-mount housing
- Choice of HART 7, BRAIN Protocol or FOUNDATION Fieldbus ITK 6 Protocol
- Local Parameter Setting function (Indicator model)
- Advanced diagnosis
Ordering Information
| Model | YTA710 | Temperature Transmitter |
| Output signal | -F | Digital communication (FOUNDATION Fieldbus protocol) |
| A | Always A (Global) | |
| Sensor input | 2 | Double |
| Housing code | C | Stainless |
| Electrical connection | 4 | M20 female |
| Integral indicator | D | Digital indicator with Local Operating Switch |
| Mounting bracket | K | 316 SST or ASTM316L stainless steel 2-inch vertical pipe mounting bracket |
| IECEx | /SU25 | Fieldbus: [Intrinsically safe ia approval] Applicable Standard: IEC 60079-0, IEC 60079-11 Certificate No. IECEx FMG 16.0014X Ex ia IIC T4 Ga Ex ic IIC T4 Gc Ex ia [ia Da] IIIC T135°C Db Ambient Temperature: –55 to +60°C for T4 (Ex ia) Ambient Temperature: –30 to +60°C for IIIC (Ex ia) –30 to +70°C (Ex ic) Enclosure: IP66/IP67 Overvoltage category: I Electrical parameters (Ex ia) Supply/Output circuit: Terminals: +, – FISCO field device or Ui=30V, Ii=300mA, Pi=1.2W, Ci=2.2nF, Li=0mH Sensor circuit: Terminals: 1, 2, 3, 4, 5 Uo=6V, Io=90mA, Po=135mW, Co=10µF, Lo=3.9mH Electrical parameters (Ex ic) Supply/Output circuit: Terminals: +, – FISCO field device or Ui=32V, Ci=2.2nF, Li=0mH Sensor circuit:Terminals: 1, 2, 3, 4, 5 Uo=6V, Io=90mA, Po=135mW, Co=10µF, Lo=3.9mH Dielectric strength: 500 V a.c.r.m.s.,1 min (Without /A) [Flameproof and Dust Ignition Proof Approval] Same as SF2 |
- Estimated Lead Time: 3 – 4 Months
- Shipping Weight: 8 Kg

Rosemount
Gauge Pressure
Differential Pressure
Absolute Pressure
Rosemount Level Transmitter
Yokogawa
ABB
E+H
HoneyWell
Micro Motion Coriolis
Rosemount
Yokogawa
E+H





Valves&Actuators